Chapter 5 Troubleshooting the 1756-HYD02 Module

Using the OK Indicator

The module’s OK indicator is shown below.

The table below explains the OK indicator.

OK indicator

43454

OK Indicator Displays

If the OK
indicator
displays:

The module status is:

Take this action:

Off

The module is not operating.

• Apply chassis power.
• Verify the module is completely inserted into the

chassis and backplane.

Flashing green
light

The module has passed internal diagnostics, but it is not
communicating axis data over the backplane.

• Configure the module to begin communications.
• If you have configured the module, check the slot

number in the 1756-HYD02 Properties dialog box.

Steady green
light

One of the following:

· Axis data is being exchanged with the module.
· The module is in the normal operating state.

None

Flashing red light

One of the following:

• A major recoverable failure has occurred.
• A communication fault, timer fault, or NVS update is

in progress.

• The OK contact has opened.

If a Non-Volatile Storage (NVS) update is in progress,
complete the NVS update.

If an NVS update is not in progress, follow these steps:

1. Check the Servo Fault word for the source of the error.

2. Clear the servo fault condition using the Motion Axis

Fault Reset instruction.

3. Resume normal operation.

4. If the flashing persists, reconfigure the module.

Steady red light

One of the following:

• A potential non- recoverable fault has occurred.
• The OK contact has opened.

Follow these steps:

1. Reboot the module.

2. If the solid red persists, replace the module.