Specifications Appendix A

Radiated RF Immunity

IEC 61000-4-3:
10V/m with 1kHz sine-wave 80%AM from 80MHz
to 2000MHz
10V/m with 200Hz 50% Pulse 100%AM at
900Mhz

EFT/B Immunity

IEC 61000-4-4:
±2kV at 5kHz on signal ports

Surge Transient Immunity

IEC 61000-4-5:
+2kV line-earth (CM) on shielded ports

Conducted RF Immunity

IEC 61000-4-6:
10Vrms with 1kHz sine-wave 80%AM from 150kHz
to 80MHz

Enclosure Type Rating

None (open-style)

Certifications
(when product is marked)

UL

UL Listed Industrial Control Equipment

CSA

CSA Certified Process Control Equipment

CSA

CSA Certified Process Control Equipment
for Class I, Division 2 Group A,B,C,D
Hazardous Locations

CE

(5)

European Union 89/336/EEC EMC
Directive, compliant with:

EN 50082-2; Industrial Immunity
EN 61326; Meas./Control/Lab.,
Industrial Requirements
EN 61000-6-2; Industrial Immunity
EN 61000-6-4; Industrial Emissions

C-Tick

(4)

Australian Radiocommunications Act,
compliant with:

AS/NZS 2064; Industrial Emissions

(1)

This specification represents the maximum LTD input resolution that the 1756-HYD02 module can accept. The
module does not require that you connect an LDT with this level of resolution.

(2)

Maximum wire size requires the extended-depth RTB housing (1756-TBE).

(3)

Use the conductor category information for planning conductor routing as described in the system level
installation manual.

(4)

Refer to Industrial Automation Wiring and Grounding Guidelines, publication number 1770-4.1.

(5)

See the Product Certification link at www.ab.com for Declarations of Conformity, Certificates, and other
certification details.