Chapter 2 Installing the 1756-HYD02 Module

Wiring the Home Limit Switch Input

The home limit switch inputs to the servo module are designed for 24V
nominal operation. These inputs should be wired for current sourcing
operation.

Wiring the OK Contacts

A set of isolated solid- state OK relay contacts is provided for optional
interface to an E- stop string, which controls power to the associated pumps.
The OK contacts are rated to drive an external 24V pilot relay, for example,
Allen-Bradley 700-HA32Z24, whose contacts can be incorporated into the
E-Stop string.

From 1756-HYD02

HOME

IN_COM

+

43396

24V dc

Field Power

Supply

General cable
C0720

From 1756-HYD02

+OK
-OK

24V dc

Field Power

Supply

+

43397

OK Pilot
Relay

43398

OK Pilot
Relay
Contacts

Start

Stop

CR1

CR1

CR1

M1

24V AC/DC
or 120VAC
typical

General cable
C0720