Rockwell Automation 1770-HT8 SMART TRANSMITTER User Manual

Page 103

Advertising
background image

Communicating with the Smart

Transmitter Interface

Chapter 4

Communicating with the Smart Transmitter

Interface

4-38

Figure 4.14

Example Full Duplex DF1 Command Ć Enable Poll and Response Mode

DLE

STX

DST

SRC

CMD

STS

TNS

FNC

LEN

Smart Transmitter Interface

Packet

DLE

ETX

BCC

10

02

OF

00

95

04

01

FF

00

00

10

03

Figure 4.15

Half Duplex DF1 Packet sent by a Host Computer to the Smart Transmitter Interface

DLE

90079

SOH STN DLE

APPLICATION DATA DLE ETX BCC/CRC

CMD

STS

TNS

FNC

SCMD

CHN

CTL

PRM

DATA

LEN

DATA

Smart Transmitter

Interface Packet

Data Link

Layer Packet

Since message is from host to Smart Transmitter Interface

DLE = data link escape control character (10" hex)

SOH = start of header control character (01" hex)

STN = Smart Transmitter Interface station address in hexadecimal

STX = start of text control character (02 hex")

DST = Smart Transmittter Interface station address in hexadecimal

SRC = host station address in hexadecimal

CMD = OF" hexadecimal

STS = status byte

TNS = tranxaction number (2 bytes)

FNC = 95" hexadecimal

LEN = length of Smart Transmitter Interface Packet in bytes

SCMD = Smart Transmitter Interface Command

CHN = Smart Transmitter Interface Channel

CTL = Smart Transmitter Interface Control

PRM = Smart Transmitter Interface Parameter

ETX = end of text control character (03" hex)

BCC/CRC = Block Check or CRC bytes

STX DST SRC

Figure 4.16

Example Half Duplex DF1 Command Ć Enable Poll and Response Mode

DLE SOH STN DLE STX DST SRC CMD STS

TNS

FNC LEN

Smart Transmitter

Interface Packet

DLE ETX BCC

10

01

10

02

0F

00

95

04

01

FF

00

00

10

03

Advertising