Installing the Smart Transmitter Interface

Products

Chapter 2

2-19

Figure 2.17

Grounding Analog I/O

90045

1 2 3 4 5 6 7 8 RTN SH

To Analog I/O

10 position COMBICON plug

10 position COMBICON connector on Terminal Block

The Communications Controller requires an external 24 VDC power
supply with

" 1% voltage regulation. The power supply must provide the

Communications Controller with 200 mA of current. It must also provide
an additional 100 mA of current for each Terminal Block that is connected
to the Communications Controller. For example, the setup in Figure 2.3
requires a 24 VDC power supply that can provide at least 500 mA. Please
refer to Appendix C if your cable length requirement exceeds those shown
in Figure 2.3 to Figure 2.5. For recommended power supplies see
Appendix C, Table C.A.

Fuses for the Communications Controller

Overload protection for external power is provided by a 1 Amp
user-replaceable fuse located immediately below the power connector on
the Communications Controller. The fuse is UL 198G and CSA 22.2, No.
59 rated, 5mm x 20mm, 250V fast acting.

Supplying Power to the

Communications Controller

and Terminal Blocks

Advertising