2ć23, Termination – Rockwell Automation 1770-HT8 SMART TRANSMITTER User Manual

Page 48

Advertising
background image

Installing the Smart Transmitter Interface

Products

Chapter 2

2-23

Figure 2.20

RIO Connector

90014

POWER

RIO

Twinaxial Cable (1770-CD)

Blue

Clear

Shield

1 SH 2

RIO

The pinout is:

Signal

Label

Cable

A1

1

Blue wire

A2

SH

Shield

A3

2

Clear wire

Use Twinaxial Cable (1770-CD) for the RIO connections. Maximum
length for the cable depends on the baud rate:

For this baud rate:

Maximum cable length is:

57600

10,000 feet (3,048 m)

115200

5,000 feet (1,524 m)

230400

2,500 feet (762 m)

Termination

Terminate the farthest physical nodes on the RIO link with a 150 or 82
Ohm termination resistor. If the Communications Controller is the last
device on the RIO link, connect a 1/2 watt resistor across pins 1 and 2 of
the plug. The value of the resistor depends on the Remote I/O baud rate:

For this baud rate:

Use this terminating resistor:

AllenĆBradley Part Number

57600

150W

#740018Ć29

115200

150W

#740018Ć29

230400

82W

#740018Ć23

Advertising
This manual is related to the following products: