Connector and pinout – Rockwell Automation 1770-HT8 SMART TRANSMITTER User Manual

Page 33

Advertising
background image

Installing the Smart Transmitter Interface

Products

Chapter 2

2-8

Connector and Pinout

Attach the 17 position Phoenix COMBICON plugs (supplied) to each end
of the cable (see Figure 2.6) then plug them into the units. Use the bare
wire for chassis ground (to be connected at one end only, preferably to the
Communications Controller end). Use only one twisted pair for each

"

pair of signals. The colors in the table below are intended as examples
only. You can use any pair you like for any pair of signals. The pinout for
the connector is in the table below.

Signal

Pin

Examples of Colors

Chassis Ground

1 (Shield)

Bare Silver

+24 VDC

2 (Power)

Red and White twisted pair;

Red is VDC White is Ground

Signal Ground

3 (Control)

Red is VDC, White is Ground

(see Appendix C)

+ Transmit Enable

4 (Control)

Red and Black twisted pair;

Red is + Black is

- Transmit Enable

5 (Control)

Red is +, Black is -

+ Channel Select 1

6 (Control)

Blue and Black twisted pair

Blue is + Black is

- Channel Select 1

7 (Control)

Blue is +, Black is -

+ Channel Select 2

8 (Control)

White and Black twisted pair;

White is + Black is

- Channel Select 2

9 (Control)

White is +, Black is -

+ Channel Select 3

10 (Control)

Orange and Black twisted pair;

Orange is + Black is

- Channel Select 3

11 (Control)

Orange is +, Black is -

+ Channel Select 4

12 (Control)

Brown and Black twisted pair;

Brown is + Black is

- Channel Select 4

13 (Control)

Brown is +, Black is -

+ Channel Select 5

14 (Control)

Green and Black twisted pair;

Green is + Black is

- Channel Select 5

15 (Control)

Green is +, Black is -

+ HART Tx/Rx

16 (Control)

Yellow and Black twisted pair;

Yellow is + Black is

- HART Tx/Rx

17 (Control)

Yellow is +, Black is -

Advertising
This manual is related to the following products: