Communicating with the Smart

Transmitter Interface

Chapter 4

Communicating with the Smart Transmitter

Interface

4-24

Table 4.I

Response to Read Module Status and Statistics

Byte

Description

1

Smart Transmitter Interface Status

Bits 0,1 Ć Smart Transmitter Interface Mode

00 = Poll and Response Mode

01 = Burst Monitor Mode

10 Ć Reserved

11 = Reserved

Bit 2 Ć RAM Test

0 = passed

1 = failed

Bit 3 Ć ROM Test

0 = passed

1 = failed

Bits 4Ć7 Ć Reserved

2

Reserved

3, 4, 5, 6

Device communication status with 1 bit per channel

0 = last attempt to poll field device was successful

1 = last attempt to poll field device including retries failed

Byte 3 Ć Bit #7 = Channel 32 ... Bit #0 = Channel 25

Byte 4 Ć Bit #7 = Channel 24 ... Bit #0 = Channel 17

Byte 5 Ć Bit #7 = Channel 16 ... Bit #0 = Channel 9

Byte 6 Ć Bit #7 = Channel 8 ... Bit #0 = Channel 1

7, 8, 9, 10 Channel in Burst Monitor Mode scan list with 1 bit per channel

0 = channel not in scan list

1 = channel in scan list

Byte 7 Ć Bit #7 = Channel 32 ... Bit #0 = Channel 25

Byte 8 Ć Bit #7 = Channel 24 ... Bit #0 = Channel 17

Byte 9 Ć Bit #7 = Channel 16 ... Bit #0 = Channel 9

Byte 10 Ć Bit #7 = Channel 8 ... Bit #0 = Channel 1

11, 12

Number of BTW requests received on RIO link

Byte 11 Ć low byte

Byte 12 Ć high byte

13, 14

Number of BTW data blocks received from programmable controller

Byte 13 Ć low byte

Byte 14 Ć high byte

15, 16

Number of BTW data blocks received via passĆthrough of programmable controller

Byte 15 Ć low byte

Byte 16 Ć high byte

17 Ć 42

Reserved