4ć12 – Rockwell Automation 1770-HT8 SMART TRANSMITTER User Manual

Page 77

Advertising
background image

Communicating with the Smart

Transmitter Interface

Chapter 4

Communicating with the Smart Transmitter

Interface

4-12

Response Code

This two-byte code contains the HART field device status as sent by that
device. Field devices detecting a communications error set the most
significant bit (bit 7) of the first byte and identify the error in the other
seven bits as shown in Table 4.C. If the last message was received without
error, the field device will clear bit 7 and return a device dependent
response code in the other seven bits.

The second byte of this response code returns the operating status of
HART field devices as indicated in Table 4.D. This byte may default to 0
when a communications error occurs as indicated by bit 7 of the first byte
being set.

Important: The host processor should ignore any values in the data field
when a communications error is detected.

Table 4.C

HART Protocol Ć Communication Error Code

Bit

Error Code

Description

7

Communications Error

If set, the field device has detected a communications

error. Bits 0 Ć 6 indicate the type of error.

6

Vertical Parity Error

The parity of one or more of the bytes received by the

HART field device is incorrect.

5

Overrun Error

At least one byte of data in the receive buffer of the

HART field device was overĆwritten before it was read.

4

Framing Error

The stop bit of one or more bytes received by the HART

field device was not detected.

3

Longitudinal Parity Error

The longitudinal parity calculated by the HART field

device does not match the longitudinal parity byte at the

end of the packet.

2

Reserved

Set to 0.

1

Buffer Overflow

The packet is too long for the receive buffer of the

HART field device.

0

Undefined

Not defined at this time.