Rockwell Automation 1770-HT8 SMART TRANSMITTER User Manual

Page 94

Advertising
background image

Chapter 4

C

Communicating with the Smart

Transmitter Interface

4-29

Word 01: Smart Transmitter Interface control hexadecimal 00 indicating

a response is required from the Smart Transmitter Interface (low byte);
Smart Transmitter Interface parameter hexadecimal 00 (high byte).

Word 02: HART delimiter hexadecimal 02 indicating an STX frame

with a short frame address (low byte); HART short frame address
hexadecimal 80 indicating primary master, and logical and slave
addresses 0 (high byte).

Word 03: HART command hexadecimal 00 (low byte); HART packet

byte count of hexadecimal 00 (high byte).

Word 04: HART packet check byte set to 0 (low byte); zero padding

(high byte).

Table 4.N

Smart Transmitter Interface to Programmable Controller Ć BTR Data Short Frame

Format for Response to Hart Command 0

Octal Bits

17

16

15

14

13

12

11

10

07

06

05

04

03

02

01

00

Decimal Bits

15

14

13

12

11

10

09

08

07

06

05

04

03

02

01

00

Word 00

Smart Transmitter Interface Channel Number

Smart Transmitter Interface Command

Word 01

Smart Transmitter Interface Status

Smart Transmitter Interface Error Code

Word 02

HART Address

HART Delimiter

Mas

Adr

Bur

Mde

Logical

Address

Slave Address

Lng

Frm

0

0

0

0

Frame Type

Word 03

Byte Count

HART Command

Word 04

HART Response Code

Second Byte Count

First Byte

Word 05

Manufacturer Identification

Code

1

1

1

1

1

1

1

0

Word 06

Number of

Preambles

Manufacturer's Device

Type Code

Word 07

Transmitter Specific

Revision

Universal Command

Revision

Word 08

Hardware

Revision

Software

Revision

Word 09

Device ID

(Most Significant Byte)

Flags

Word 10

Device ID

(Least Significant Byte)

Device ID

Middle Byte

Word 11

0

0

0

0

0

0

0

0

Check Byte

Advertising
This manual is related to the following products: