Rockwell Automation 1770-HT8 SMART TRANSMITTER User Manual

Page 71

Advertising
background image

Communicating with the Smart

Transmitter Interface

Chapter 4

Communicating with the Smart Transmitter

Interface

4-6

Figure 4.3

HART Poll Packets Ć Smart Transmitter Interface to HART Field Device (Short Frame

Format)

90069

Hart Command

Short Frame HART Address

HART Delimiter

Preamble

Byte Count

Data

Check Byte

Slave Address Bits

Logical Address Bits

Master Address Bit

0 Secondary Master

1 Primary Master

Frame Type

010 STX Frame

Reserved

Long/Short Frame Bit

0

Short

1

Long

0 0 0 0 0

0

Figure 4.4

HART Poll Packets Ć Smart Transmitter Interface to HART Field Device (Long Frame

Format)

90070

HART Command

Long Frame HART Address

HART Delimiter

Preamble

Byte Count

Data

Check Byte

Higher Order

Slave Address Bits

Master Address Bit

0 Secondary Master

1 Primary Master

Frame Type

010 STX Frame

Reserved

Long/Short Frame Bit

0

Short

1

Long

1 0 0 0 0

0

Advertising