Loop power led power fuse power connector, User writeable area – Rockwell Automation 1770-HT8 SMART TRANSMITTER User Manual

Page 14

Advertising
background image

Introducing the Smart Transmitter

Interface

Chapter 1

1-3

1770ĆHT8/16 Terminal Block

The Terminal Blocks pass both analog and digital signals to and from the
HART field devices. The analog signal is passed on to devices such as the
Allen-Bradley 1771-IFE Analog I/O module. The digital signal is routed to
the Communications Controller.

Each Terminal Block provides either 8 (1770-HT8) or 16 (1770-HT16)
channels. Each channel has connection points for HART field devices and
Analog I/O modules, loop fuses and loop power selection jumpers. Any
combination of 8 and 16 channel Terminal Blocks can be used to make up
the 32 channel maximum. The board address jumpers (see Figure 1.2 and
Figure 1.3) indicate to the Communications Controller which set of
channels a particular Terminal Block will use. These are set when the
Terminal Block is installed (see Chapter 2).

Figure 1.2

1770ĆHT8 8 Channel Terminal Block

90018

Board Selected LED

Connection to Communications

Controller or other Terminal Blocks

Board Address

Jumpers

Analog I/O Module

Connector

1 2 SH 1 2 SH 1 2 SH 1 2 SH

1

1 2 3 4 5 6 7 8 RTN SH

CH 1 CH 2 CH 3 CH 4

Loop

Power

LED

Power Fuse Power Connector

E D

1 2 SH 1 2 SH 1 2 SH 1 2 SH

CH 5 CH 6 CH 7 CH 8

Jumpers to select Loop Power

HART Transmitters -

Connectors

Loop Fuses

8 CHANNEL

TERMINAL BLOCK

17

+ -

Loop Power

CATALOG NO. 1770-HT8 VOLTS 24 VDC

HT1/HT8/HT16 INTERCONNECT

JP1

E D

JP1 JP1

E D

JP1

E D E D

JP1

E D

JP1 JP1

E D

JP1

E D

User writeable area

Advertising