Cable Length and Power Supply

Requirements

Appendix C

C-3

Figure C.3

Determining Maximum Cable Lengths for Linear Connection

90055

1170-HT1

a

b

d

1770-HT8

1770-HT8

1770-HT8

1770-HT8

c

Control Signals

Total cable lengths <= 1000 ft

or <= 305 m

+24 VDC Power Ċ Pin 2

a + b + c + d <= 1000 / (0.065 * R)

where R = cable resistance per 1000 ft

or a + b + c + d <= 1/(0.065 * R)

where R = cable resistance per meter

Figure C.4 illustrates the formula as it applies to a star connection
configuration in which each Terminal Block is wired directly to the
Communication Controller with its own cable.

Figure C.4

Determining Maximum Cable Lengths for Star Connection

90059

1170-HT1

d

1770-HT8

1770-HT8

1770-HT8

1770-HT8

Channel Select and Data Signals

a + b + c + d <= 1000 ft

or a + b + c + d <= 305 m

+24 VDC Power Ċ Pin 2

a, b, c, and d <= 1000 / (0.065 * R)

where R = cable resistance per 1000 ft

or a, b, c, and d <= 1/(0.065 * R)

where R = cable resistance per meter

c

b

a