HART Address

When field devices respond to HART polls they send packets with the
same short or long frame address format used in the poll. The field device
sets or clears the master address bit depending on which master the
response is for. If the device is also bursting data, it sets the burst mode
address bit; otherwise it clears this bit. You must program the host
processor to verify that the address field in a HART Response packet is
correct before it processes the remaining data in the packet.

Figure 4.6

HART Response or Burst Data Packets Ć HART Field Device to Smart Transmitter

Interface (Short Frame Format)

90071

HART Command

Short Frame HART Address

HART Delimiter

Byte Count

Response Code

Data

Check Byte

Slave Adddress Bits

Logical Address Bits

Device Burst Mode Bit

0 Disabled

1 Enabled

Master Address Bit

0 Secondary

Master

1 Primary Master

Frame Type

001 Burst Frame

110 ACK Frame

Reserved

Long/Short Frame Bit

0

Short

1

Long

0 0 0 0 0

Preamble

When the host processor requests data from the Burst Data table, the
packet that is received contains either a short frame or long frame address,
depending on the field device which sent that data to the Smart Transmitter
Interface. The master address bit may also be in either state, as field
devices alternate this bit between primary and secondary master when
bursting data.