Chapter 4

C

Communicating with the Smart

Transmitter Interface

4-13

Table 4.D

HART Field Device Error Codes

Bit

Error Code

Description

7

Field Device Malfunction

An internal hardware error or failure has been detected

by the HART field device.

6

Configuration Changed

A write or set command has been executed by the

HART field device.

5

Cold Start

Power has been removed and reapplied resulting in the

reinstallation of the setup information. The first HART

command to recognize this condition automatically

resets this flag. This flag may also be set following a

master reset or self test.

4

More Status Available

More status information is available and can be read

using command #48, Read Additional Status

Information.

3

Primary Variable Analog

Output Fixed

The analog and digital outputs for the primary variable

are held at their requested value. They will not respond

to the applied process.

2

Primary Variable Analog

Output Saturated

The analog and digital outputs for the primary variables

are beyond their limits and no longer represent the true

applied process.

1

NonĆPrimary Variable Out of

Limits

The process applied to a sensor, other than that of the

Primary Variable, is beyond the operating limits of the

device. To identify the variable, use command #48,

Read Additional Status Information.

0

Primary Variable Out of

Limits

The process applied to the sensor for the primary

variable is beyond the operating limits of the device.

Data

This field contains the number of bytes of response data associated with
the command number specified in the command field. An application on
the host processor can use this data as required.

Check Byte

This one byte field contains a check byte which the Smart Transmitter
Interface uses to verify the validity of data received from the field device.
If the Smart Transmitter Interface detects a bad check byte, it resends
HART polls to the device until either a valid response is received or the
maximum number of retries have occurred.