Rockwell Automation 1770-HT8 SMART TRANSMITTER User Manual

Page 104

Advertising
background image

Chapter 4

C

Communicating with the Smart

Transmitter Interface

4-39

In both full duplex and half duplex mode the DF1 responses from the
Smart Transmitter Interface are identical. These responses are sent
immediately by the Smart Transmitter Interface in full duplex mode.
However, in half duplex mode the host must first send a poll to the Smart
Transmitter Interface before it will send the DF1 Response. Figure 4.17
and Figure 4.18 illustrate the format and an example of these responses.

Figure 4.17

DF1 Packet sent by the Smart Transmitter Interface to a Host Computer

DLE

90080

STX

DST

SRC

APPLICATION DATA

DLE

ETX

BCC/CRC

CMD

STS

TNS

SCMD

CHN

ERR

STA

DATA

LEN

DATA

Smart Transmitter

Interface Packet

Data Link

Layer Packet

Since message is from host to Smart Transmitter Interface

DLE = data link escape control character (10" hex)

STX = start of text control character ("02"hex)

DST = host station address in hexadecimal

SRC = Smart Transmitter Interface station address in hexadecimal

CMD = 4F" hexadecimal

STS = status byte

TNS = transaction number (2 bytes)

LEN = length of Smart Transmitter Interface Packet in bytes

SCMD = Smart Transmitter Interface Command

CHN = Smart Transmitter Interface Channel

ERR = Smart Transmitter Interface Error Code

STA = Smart Transmitter Interface Status

ETX = end of text control character (03" hex)

BCC/CRC = Block Check or CRC bytes

Advertising