Chapter 4

C

Communicating with the Smart

Transmitter Interface

4-11

Figure 4.7

HART Response of Burst Data Packets Ć HART Field Device to Smart Transmitter

Interface (Long Frame Format)

90072

Command

Long Frame HART Address

HART Delimiter

Preamble

Byte Count

Response Code

Data

Check Byte

Higher Order

Slave Address Bits

Device Burst Mode Bit

0 Disabled

1 Enabled

Master Address Bit

0 Secondary Master

1 Primary Master

Frame Type

001 Burst Frame

110 ACK Frame

Reserved

Long/Short Frame Bit

0

Short

1

Long

1 0 0 0 0

HART

HART Command

This one-byte field echoes the HART command being responded to. This is
either the last command sent to the device, or the HART command for
which burst data is being transmitted by the device. Program the host
processor to verify that this field contains the correct command before it
processes the remaining data in the packet.

Byte Count

This one-byte field indicates the number of bytes to follow this field
excluding the check byte. Valid values are 2 to 113. It indicates to the host
processor the size of the received data field.