Rockwell Automation 1770-HT8 SMART TRANSMITTER User Manual

Page 83

Advertising
background image

Communicating with the Smart

Transmitter Interface

Chapter 4

Communicating with the Smart Transmitter

Interface

4-18

Table 4.F

Smart Transmitter Interface Error Codes

Error Code

(hex)

Definition

Description

General Errors

00

No Error

The Smart Transmitter Interface processed the last received

command, and no errors were detected.

01

Downloading

Firmware

The Smart Transmitter Interface firmware is being upgraded

over the RSĆ232C port. The last received command cannot be

processed.

02

No Corresponding

BTW

The Smart Transmitter Interface received a BTR but does not

know what data is being requested. All BTRs must be

preceded by a BTW indicating what response to return in a

BTR.

03

Command Still in

Progress

The Smart Transmitter Interface is still obtaining the HART

Response from a field device and cannot respond with the

requested data. The programmable controller should reissue

the BTR request to obtain the response.

Command Errors

10

Invalid Command

The Smart Transmitter Interface command is invalid and

cannot be processed.

11

Invalid Channel

Number

The Smart Transmitter Interface channel number is invalid.

The command cannot be processed.

12

Invalid HART

Message

The HART packet encapsulated within a Smart Transmitter

Interface packet is invalid and cannot be forwarded to a field

device.

13

Invalid Channel

List

The channel list provided with the Enable Burst Monitor Mode

command contains an invalid entry or is incorrectly terminated.

The command cannot be processed.

14

Invalid Parameter

An invalid parameter is provided with the Smart Transmitter

Interface command and so it cannot be processed.

15

Invalid Control

An invalid control byte is included with the Smart transmitter

Interface command. The command cannot be processed.

16

Invalid DF1 Packet

Length

The length of the DF1 packet is not consistent with the length

specification in that packet. The command cannot be

processed.

Device Errors

20

Burst Mode Device

Not

Communicating

The Smart Transmitter Interface is not receiving burst data

from a field device in burst mode. Either Burst mode has been

turned off in the field device or it is too busy to send burst table

data. The error code is cleared once the Smart Transmitter

Interface receives new burst data from the device.

21

No Response

Received From

Device

The Smart Transmitter Interface has not received a response

from a field device after exhausting all retry attempts.

22

No Valid Burst

Data

The Smart Transmitter Interface does not have data in its

Burst Monitor Table for the requested channel. Either the

Smart Transmitter Interface was not commanded to monitor

the channel for burst data, or the field device is not in burst

mode.

Advertising