Rockwell Automation 1770-HT8 SMART TRANSMITTER User Manual

Page 110

Advertising
background image

Product Specifications

Appendix A

A-2

Electrical

DC Input Voltage

24 VDC

"1% (600 mA maximum load)

Fuse

UL 198G and CSA 22.2, No. 59 rated,
5mm x 20mm, 1.0 Amp., 250V, fast acting

Connector

Phoenix COMBICON header and plug
3 position, 12-24 AWG

Power Consumption

4.8 watts maximum

Physical

Dimensions

4.3” (10.9 cm) wide x 14.0” (35.6 cm) long x 2.7”
(6.9 cm) high

Weight

1.8 lb (0.8 kg) approximate

Mounting

DIN rail (EN 50 022 or EN 50 035)

Environmental

Operating temperature

0

_C to 60_C (32_F to 140_F)

Storage temperature

–40

_C to 60_C (–40_F to 140_F)

Operating humidity

5% to 95% (non-condensing)

1770ĆHT1 Interface

Connector

Phoenix COMBICON header and plug – 17 position,
12-24 AWG

Input

24 VDC, differential channel select signals, differential
transmit enable, differential half-duplex HART
transmit/receive

4Ć20 mA Current Loop Interfaces (see Figure A.1)

Channels

eight 4-20 mA current loops

I/O Module Connector

Phoenix COMBICON header and plug
10 position, 1 set, 12-24 AWG

I/O Module Cable Length 30 foot (9 m) maximum between the

Terminal Block and the Analog I/O module

Field Device Connector

Phoenix COMBICON header and plug
12 position, 2 sets, 12-24 AWG

Loop Fuses

UL 198G and CSA 22.2, No. 59 rated,
5mm x 20mm, 0.1 Amp., 250V, fast acting

8 Channel Terminal Block

(1770ĆHT8)

Advertising