Chapter 4

C

Communicating with the Smart

Transmitter Interface

4-33

Table 4.R

Smart Transmitter Interface to Programmable ControllerĆ BTR Data Long Frame

Format for Response to HART Command 1

Octal Bits

17

16

15

14

13

12

11

10

07

06

05

04

03

02

01

00

Decimal Bits

15

14

13

12

11

10

09

08

07

06

05

04

03

02

01

00

Word 00

Smart Transmitter Interface Channel Number

Smart Transmitter Interface Command

Word 01

Smart Transmitter Interface Status

Smart Transmitter Interface Error Code

Word 02

HART Address

HART Delimiter

Mas

Adr

Bur

Mde

Manufacturer

Identification Code

Lng

Frm

0

0

0

0

Frame Type

Word 03

Device ID

(Most Significant Byte)

Manufacturer's

Device Type

Word 04

Device ID

(Least Significant Byte)

Device ID

(Middle Byte)

Word 05

Byte Count

HART Command

Word 06

HART Response Code

Second Byte

First Byte

Word 07

Primary Variable

(Most Significant Byte)

Primary Variable

Units

Word 08

Primary Variable

(3rd Most Significant Byte)

Primary Variable

(2nd Most Significant Byte)

Word 09

Check Byte

Primary Variable

(Least Significant Byte)

Table 4.S

Example BTR Data Offset at D9:40 Ć Long Frame Format for HART 1 Command

Address

0

1

2

3

4

5

6

7

8

9

D9:40

0110

8000

A686

000D

1115

0701

0000

4220

3991

B356

Long Frame Word Contents Ć Smart Transmitter Interface to

Programmable Controller (Offset at D9:40)

Word 00: Smart Transmitter Interface Command is hexadecimal 10 (low

byte); Smart Transmitter Interface Channel is hexadecimal 01 (high
byte).

Word 01: Smart Transmitter Interface Error Code is hexadecimal 00

indicating no errors (low byte); Smart Transmitter Interface Status is
hexadecimal 80 indicating the Smart Transmitter Interface has been
reset (high byte).