Publication 1794-UM061A-EN-P - July 2006

98 Configure your Digital Module on an EtherNet/IP Network

Using RSLinx software to set the IP address

To use RSLinx to configure the EtherNet/IP module:

1. Make sure the module is installed and powered up.

2. Start RSLinx. The RSWho window opens. Navigate in RSWho to the

Ethernet network.

3. Right-click on the EtherNet/IP module (not the controller, if there is

one) and select Module Configuration.

4. Select the Port Configuration tab, choose Status Network Configuration

type, and enter the IP address and the other network parameters, if
needed.

5. Also, select the Static radio button to permanently assign this

configuration to the port. If you select Dynamic, on a power cycle, the
controller clears the current IP configuration and will again begin
sending BOOTP requests.