Configure your Digital Module on an EtherNet/IP Network
99
Using RSLogix 5000 software to set the IP address
To use RSLogix 5000 software to configure the EtherNet/IP module:
1. Make sure the module in installed and powered up.
2. Connect to the controller via a serial, or other network, connection.
3. Start RSLogix 5000 software. In the Controller Organizer, select
properties for the EtherNet/IP module.
4. Select the Port Configuration tab and specify the IP address and the
other network parameters, if needed. Click Apply and then click OK.