Publication 1794-UM061A-EN-P - July 2006

Configure Your Adapter and Digital Modules on a ControlNet Network

73

13. The network and connections are now scheduled.

14. From the main menu, choose Network>Properties. The _default dialog

appears.

Specify the following information on network parameters:

15. Specify a value for Network Update Time - the repetitive time interval in

which data can be sent on the link.

16. Specify a value for Max Scheduled Address - the highest number node

that has scheduled connections to it.

17. Specify a value for Max Unscheduled Address - the node with the

highest MAC ID that can use unscheduled time on the link.

These values are set to 99 by default. Change these values to what is
installed in your system. This saves you time because the controller will
not have to search for all of the node addresses.