Configure your Digital Module on an EtherNet/IP Network

85

Direct Connections For I/O Modules

In this example, assume that each distributed I/O module is configured for a
direct connection to the controller.

The following table calculates the connections in this example.

If you have many modules, direct connections to each module may not be
feasible because you could use up the number of connections and packets per
second supported by the module.

Refer to Rack-optimized Connections For I/O Modules on page 86 to
conserve connection use and network traffic.

EtherNet/IP Network

Controller With EtherNet/IP
Communication Module

EtherNet/IP Adapters
With I/O Modules

Digital I/O Modules

Analog I/O Modules

Digital I/O Modules

Switch

System Connections

Amount

Controller to local EtherNet/IP communication module

0

Controller to EtherNet/IP adapter

Direct connection for digital I/O module
Direct connection for analog I/O module

4
2

Total connections used 6