54 Configure FLEX I/O Digital Modules on a DeviceNet Network

Tally Memory

Requirements

The 1794-ADN FLEX I/O adapter packs the data of its I/O modules into a
contiguous block of input or output bytes. By default, the modules share
DINT elements in the scanner.

For example, to determine the amount of scanner memory required for your
adapter and its I/O modules

As an option, give each module its own memory location (DINTs) within the
scanner. This may make your programming easier. Assign one address for the
1794-ADN and all the modules that you connect to it.

Device

Input Size of

Device

(bytes)

Output Size

of Device

(bytes)

FLEX I/O adapter—1794-ADN

2

0

digital output module—1794-OB16D

2

2

digital input module—1794-IB16D

2

0

Total

6

2

Device

Address

Input Size of

Device

(bytes)

Input Memory

in Scanner

(DINTs)

Output Size

of Device

(bytes)

Output Memory

in Scanner

(DINTs)

Start/stop Buttons

1

1

1

1

Motor Starter

4

1

4

1

FLEX I/O Adapter w/modules

6

2

2

1

Total

1. Add the input bytes of each module + 2 bytes for the adapter.

2. Add the output bytes of each module (0 for the

adapter).

3. Add the totals to the main tally.

Sub Tally

Main Tally

I/
O

I/
O

I/
O

A
D
N

4

DeviceNet network