Configure Your Adapter and Digital Modules on a ControlNet Network

63

Rack-optimized connections for I/O modules

In this example, assume that each digital I/O module is configured for a
rack-optimized connection to the controller. Analog modules must be
configured for direct connections.

The table below calculates the connections in this example.

The rack-optimized connection conserves connections, but can limit the status
and diagnostic information that is available from the digital I/O modules.

To increase the number of available connections, use a rack-optimized
connection to any remote adapter with multiple digital I/O modules that allow
rack-optimized connection, instead of direct connections to those I/O
modules.

ControlNet network

I/O I/O

I/O I/O

I/O I/O

ControlNet adapter with
digital I/O modules

ControlNet adapter with
analog I/O modules

ControlNet adapter with
digital I/O modules

controller with ControlNet
communication module or
built-in communication port

System Connections:

Amount:

Controller to local ControlNet communication module

0

Controller to ControlNet adapters with digital modules

(rack-optimized connection to each adapter)

2

Controller to ControlNet adapter with analog modules

(direct connection for each analog I/O module)

0

2

total connections used: 4