Publication 1794-UM061A-EN-P - July 2006

60 Configure Your Adapter and Digital Modules on a ControlNet Network

For I/O modules, the available communication formats depend on the
module type. In general:

See online help in RSLogix 5000 programming software for specific
communication formats per I/O module.

If you have this type of I/O module:

And want:

Select a communication format that specifies:

digital module

a rack-optimized connection

Rack Optimization

a direct connection or to use
specialty features of the module,
such as diagnostics, timestamps,
or electronic fuses

or

to only listen to data from the
module.

The data your controller needs from the I/O module. For
example, if your application uses a 1756-IA16I module
in a remote chassis that must provide timestamped
input data, you should select the CST Timestamped
Input Data communication format.

A Listen Only communication format that matches the
data the I/O module is broadcasting to other controllers.

analog module

a direct connection or to use
specialty features of the module,
such as diagnostics, timestamps,
or electronic fuses

or

to only listen to data from the
module.

The data your controller needs from the I/O module. For
example, if your application uses a 1756-OF6CI module
in a remote chassis that must provide floating point
output data, you should select the Float Data
communication format.

A Listen Only communication format that matches the
data the I/O module is broadcasting to other controllers.