106 Interpret the Indicators

Diagnostic Functions for the 1794-IB16D

Ext.

Power

Wiring

Input

Status

Channel LED

Status

Open Wire

Error Bit

Short

Error Bit

Rev.

Error Bit

Module Error

Bit/LED

OFF

Open

Off

Off

0

0

0

0/OFF

On

Off

0

0

0

0/OFF

Short

Off

Off

0

0

0

0/OFF

On

Off

0

0

0

0/OFF

Normal

Off

Off

0

0

0

0/OFF

On

Off

0

0

0

0/OFF

ON

Open

Off

RED

1

0

0

1/RED

On

RED/YEL

1

0

0

1/RED

Short

Off

RED

0

1

0

1/RED

On

RED/YEL

0

1

0

1/RED

Normal

Off

Off

0

0

0

0/OFF

On

YEL

0

0

0

0/OFF

REV

Open

Off

Off

0

0

1

1/RED

On

Off

0

0

1

1/RED

Short

Off

Off

0

0

1

1/RED

On

Off

0

0

1

1/RED

Normal

Off

Off

0

0

1

1/RED

On

Off

0

0

1

1/RED

The module monitors each sensor-power port for current and voltage. It turns on the channel red LED and sets (1) the error bit when
1) the module detects a short circuit (no voltage at the sensor-port), and 2) the module detects an open wire ( no current at the
sensor-port).