108 Interpret the Indicators

Diagnostic Functions for the 1794-OB16D

Diagnostic Functions for the 1794-OB16D

ATTENTION

Each unused output port requires a dummy resistor
(20 K

Ω

+10%, 1/8 W) to mask the channel diagnostic

function.

Ext.

Power

Wiring

Output

Status

Channel LED

Status

Open Wire

Error Bit

Short

Error Bit

Rev. Error

Bit

Module Error

Bit/LED

OFF

Open

Off

Off

0

0

0

0/OFF

On

Off

0

0

0

0/OFF

Short

Off

Off

0

0

0

0/OFF

On

Off

0

0

0

0/OFF

Normal

Off

Off

0

0

0

0/OFF

On

Off

0

0

0

0/OFF

ON

Open

Off

RED

1

0

0

1/RED

On

YEL

0

0

0

0/OFF

Short

Off

Off

0

0

0

0/OFF

On

RED

0

1

0

1/RED

Normal

Off

Off

0

0

0

0/OFF

On

YEL

0

0

0

0/OFF

REV

Open

Off

Off

0

0

1

1/RED

On

Off

0

0

1

1/RED

Short

Off

Off

0

0

1

1/RED

On

Off

0

0

1

1/RED

Normal

Off

Off

0

0

1

1/RED

On

Off

0

0

1

1/RED

The module monitors each output channel. It turns on the channel red indicator and sets (1) the error bit when 1) the module detects a
short circuit (the output signal is active at a channel and the corresponding output voltage is low), and 2) the module detects an open wire
(the output signal is inactive at a channel and the corresponding output voltage is high).