Interpret the Indicators

105

For 3-wire sensors:

an open fault will be detected when an open occurs on either the
sensor-power wire, the sensor (-V) wire, or the high-current portion of
the input sensor field device.

an open on the input-signal wire or low-current portion of the input
sensor field device will not be detected, and will be seen as an
off/inactive input sensor field device.

a shorted circuit from the sensor-power wire to sensor common (-V) is
detected as short fault (no voltage at the sensor-power port).

a shorted circuit from the sensor-power wire to the input-signal wire
cannot be detected. It will appear as an on/active input device.

a shorted circuit from the input-signal wire to sensor common (-V), with
the input sensor field device in the off-state, cannot be detected. It will
appear as an off/inactive input sensor device.

a shorted circuit from the input-signal wire to sensor common (-V), with
the input sensor field device in the on-state, is detected as a short fault if
the sensor field device can pass the sensor power short circuit current.

a shorted 3-wire input sensor device may or may not be detected,
depending on which portion of the input sensor device is shorted.

a shorted circuit to the DIN rail or chassis ground cannot be detected.

Diagnostic Functions for the 1794-IB16D

Each unused sensor port requires a dummy resistor to mask the channel
diagnostic function.

Open

OFF or ON

OFF

Red

Red

Open wire
& Module

No current in Sensor Power terminal-
Missing sensor, cut Sensor Power or Input Signal wire

Short

OFF

OFF

Red

Red

Short & Module

Shorted Sensor Power/ Common

OFF

ON

OFF

Yellow

None

Shorted Sensor Power/ Input Signal

OFF

OFF

OFF

OFF

None

Shorted Input Signal/ Common

ON

OFF

Red

Red

Short & Module

Shorted Input Signal/ Common

1

Reverse
User
Power

OFF or ON

OFF

Red

OFF

Reverse & Module

User power supply wiring is reversed

1

If sensor can pass Sensor Power short circuit current

Fault

Device/Input State

Indicators

Error Bit
Status

Conditions

Field
Device

Input
Status

Module
Fault

Channel
Fault

Open

OFF

OFF

Red

Red

Open wire
&
Module

No current in Sensor Power terminal-
Missing sensor, cut Sensor Power or
Common wire

OFF or ON

OFF

OFF

OFF

None

Cut Input Signal wire

Short

OFF

OFF

Red

Red

Short & Module

Shorted Sensor Power/ Common

OFF

ON

OFF

Yellow

None

Shorted Sensor Power/ Input Signal

OFF

OFF

OFF

OFF

None

Shorted Input Signal/ Common

ON

OFF

Red

Red

Short & Module

Shorted Input Signal/ Common

1

Reverse User Power

OFF or ON

OFF

Red

OFF

Reverse & Module

User power supply wiring is reversed

1

If sensor can pass Sensor Power short circuit current