Wiring output loads – Rockwell Automation 1794-OB16D FLEX I/O Diagnostic Modules User Manual User Manual

Page 30

Advertising
background image

Publication 1794-UM061A-EN-P - July 2006

28 About the FLEX I/O Diagnostic Output Module

Wiring Output Loads

You can use the 1794-OB16D diagnostic module with the 1794-TB2,
1794-TB3, or 1794-TB3S terminal base units.

User power can be wired to the (+) voltage and common terminals directly, or
power can be daisychained from the FLEX I/O terminal base units on the
DIN rail. Output channels are not isolated from one another. All 16 channels
share a common return (group isolation from FLEX I/O system-side logic
voltages).

17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33

0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15

16

35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51

34

Output Channel 0-15

Common

(1794-TB3 shown)

-V

Voltage
In +V

Voltage
Out +V

Voltage (24V dc)

Terminals 35 thru 50 not available on 1794-TB2

A

B

C

Common

-V

Common

0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15

0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15

FLEX TB2/3/3S
Terminal Base

A0-A15

B17-B32

C34

B16

Output

Common

V+

V-

Output
Device

24V dc
External User
Power Supply