Publication 1794-UM061A-EN-P - July 2006

About the FLEX I/O Diagnostic Output Module

29

You must connect dummy resistors to unused sensor power ports to mask the
diagnostic function. If these external resistors are not used, the module’s
sensing circuitry will not detect the intended voltage or current and signal a
module fault. The channel fault indicator and the module’s fault indicator will
light, and the module’s open and error bits are set, thus rendering fault
detection of the remaining channels useless. The recommended value of this
dummy resistor is 10 K

Ω

(+10%), 1/8 W (or larger). The resistor is wired

between unused output channels and common. The figure depicts wiring of a
dummy resistor.

Diagnostic Fault Detection

The module monitors current and voltage at each output channel terminal,
and monitors the user supply for reverse supply voltage. The figure below
shows the location of these fault monitors within the 1794-OB16D diagnostic
output module.

User Power

Open Wire
Detect
Current

Shorted
Output
Monitor

Fault Indicator

-

Reverse

Short

Open

Output

V+

Open Wire
Monitor

Reverse
Voltage
Monitor

Output Indicator

Output

Fl

exb

us

In

te

rf

ac

e

+

40117C

Current Limiting
Thermal Prot.
Output FET