Configure Your Adapter and Digital Modules on a ControlNet Network

59

Select a

Communication Format

When you configure a remote ControlNet communications module or an I/O
module, you select a communication format. The communication format you
choose determines the data structure for the tags that are associated with the
module. Many I/O modules support different formats. Each format uses a
different data structure.

The communication format that you choose also determines:

• Direct or rack-optimized connection
• Ownership of outputs

For a remote ControlNet communications module, you must select one of the
formats listed below.

Use this communication format

with a remote ControlNet

communication module:

In these scenarios:

None

• All of the remote I/O communicating with a

controller via the remote ControlNet
communication module use a Direct Connection
communication format.

• The connection is used for scheduled

peer interlocking.

• When I/O will be predominately direct

connections.

• When multiple controllers control the outputs in

the chassis

Rack optimized

• Some or all of the remote I/O communicating

with a controller via the remote ControlNet
communication module use a Rack Optimized
communication format.

• To minimize ControlNet bandwidth when using

large volume of digital I/O.

• If only one controller will control the I/O.

Rack optimized - Listen only

• Some or all of the remote I/O communicating

with a controller via the remote ControlNet
communication module use a Rack Optimized
communication format.

• The connection is going to read inputs but is not

going to be controlling outputs.