56 Configure FLEX I/O Digital Modules on a DeviceNet Network
Set the Address of the
Adapter
To set the address of the FLEX I/O DeviceNet adapter 1794-ADN:
For more information on using DeviceNet in Logix5000 control systems, see
.
1. To change the address, press the button above or below a number.
2. Connect the adapter to the network.
3. Turn on power to the adapter.
4. Check the Mode/Net STATUS light.
If:
Then the:
Green (Flashing or
Solid)
address is OK
Solid Red
address and/or baud rate conflict with another device
Off
device is waiting to set its baud rate
When autobaud is on, the device waits until it hears another device
on the network. It then sets its baud rate to that of the other device.