Chapter 3

Configure the Adapter

3.

Apply power to the 2100-ENET adapter.

4.

From the File menu, choose Open.

5.

Select your saved configuration data file and click OK.

The node configuration appears in the Relation List window.

6.

To change the IP address or enable BOOTP, right-click the node and
choose Properties.

7.

Cycle power to the 2100-ENET adapter.

The selected action takes effect upon powerup.

If the configuration file does not exist, click New in the Relation List
window and enter the Ethernet Address (MAC) printed on the product
data nameplate, along with the previously assigned IP address to add the
unit to the Relation List. Further actions described above can then be
executed on the desired unit.

Set the Data Rate

By default, the adapter is set to autodetect, so it automatically detects the data rate
and duplex setting used on the network.

Set the I/O Configuration

The I/O configuration determines the data that is sent to and from the E3 Plus or
825-P. Both the E3 Plus and the 825-P use Input and Output Assemblies to
determine the data being sent. See

Table 1 on page 42

for a list of input and

output assemblies supported by the Add-on Profile (AOP). For instructions on
how to change the input and output assemblies of the E3 Plus or 825-P, refer to
the appropriate user manual.

TIP

The end device’s DeviceNet address is configured for node 63 by following the
instructions provided in the appropriate end device user manual. The data rate
is configured for 500 Kpbs by following the instructions provided in the
appropriate end device user manual.