Controllogix controller image – Rockwell Automation 2100-ENET CENTERLINE 2100 Motor Control Centers EtherNet/IP Network Adapter User Manual

Page 42

Advertising
background image

42

Rockwell Automation Publication 2100-UM006A-EN-P - July 2013

Chapter 5

Using the I/O

ControlLogix Controller Image

In all instances of the E3 Plus Add-on Profile, the controller tags are predefined
in

Table 1

. In RSLogix 5000 software, version 16 or later, and the Classic Profile

for version 15, these controller tags are automatically created for you. However,
when using the Generic Profile (See

Using the RSLogix 5000 Generic Profile (all

versions) on page 35

) in RSLogix 5000 software, these controller tags are not

descriptive or defined.

The following tables show how to configure the E3 Plus based on the settings
chosen in setting up the E3 Plus Add-on Profile in RSLogix 500 software.

Table 1

shows how the Input and Output Assemblies are configured in the E3 Plus.

Table 2

shows the general tag names for specific assemblies. These assemblies are

not changed from those reflected in the E3 Plus user manual. For more detailed
information on the tables below, reference E3 and E3 Plus Solid-State Overload
Relay User Manual, publication

193-UM002

.

Table 1: Input and Output Assembly Configuration for the E3 Plus per Connection Type

Connection

Output
Assembly (59)

Input Assembly
(60)

EC1 Connection

Parameter Based (Default)

103

100

Parameter Based

103

100

Status

103

106

Parameter via DataLink

110

111

EC2, EC3, EC4 Connection

Parameter Based (Default)

105

100

Parameter Based

105

100

DeviceLogix + Status

140

141

Parameter via DataLink

110

111

EC5 Connection

Parameter Based (Default)

105

100

Parameter Based

105

100

DeviceLogix + Status

140

142

Parameter via DataLink

110

111