Rockwell Automation 2100-ENET CENTERLINE 2100 Motor Control Centers EtherNet/IP Network Adapter User Manual
Page 51
![background image](/manuals/580622/51/background.png)
Rockwell Automation Publication 2100-UM006A-EN-P - July 2013
51
Using Explicit Messaging
Chapter 6
ControlLogix Example Ladder Logic Program to Write a Single Parameter (version 15 or later)
A Parameter Write message is used to write to a single parameter. This write
message example writes a value to parameter 28 - [FLA Setting] in an E3 Plus
module.
Table 5: Example Controller Tags to Write a Single Parameter
Figure 13: Example Ladder Logic to Write a Single Parameter
ControlLogix Controller – Formatting a Message to Write a Single Parameter (version 15 or
later)
Figure 14: Parameter Write Single Message Configuration Dialog Boxes
Operand
Controller Tags for Single Write Message
Data Type
XIC
Execute_Single_Write_Message
BOOL
MSG
Single_Write_Message
MESSAGE