Logix controller i/o messaging – Rockwell Automation 2100-ENET CENTERLINE 2100 Motor Control Centers EtherNet/IP Network Adapter User Manual

Page 35

Advertising
background image

Rockwell Automation Publication 2100-UM006A-EN-P - July 2013

35

Configure the I/O

Chapter 4

Using the RSLogix 5000 Generic Profile (all versions)

The basic RSLogix 5000 Generic Profile is recommended only when the
following is true:

A specific profile in other versions of RSLogix 5000 software is
unavailable.

Users are already familiar with a Generic Profile and do not want to
convert an existing project to a Classic Profile, version 15, or a Add-on
Profile, version 16 or later.

A project must maintain specific revision level control.

The controller cannot be taken offline. RSLogix 5000 software, version 16
or later, enables the Generic Profile to be added while the controller is
online and in the Run mode.

If the Input Data types do not support the Input and Output Assembly
combination desired.

Logix Controller I/O Messaging

RSLogix 5000 software is used to configure I/O messaging between a Logix
controller and an E3 Plus EtherNet/IP network adapter on an EtherNet/IP
network. Follow these steps to configure a Logix controller for I/O messaging.

1.

Right-click the EtherNet/IP network scanner in I/O Configuration and
choose New Module to open the Select Module Type dialog box.

2.

Select Generic Ethernet Module and click OK.

3.

Enter a name for the E3 Plus EtherNet/IP network adapter.

The name creates a tag in RSLogix 5000 software that can be used to read
and write data from the E3 Plus EtherNet/IP network adapter.

New Module: Select Module Type

Advertising