PORT Status Indicator

This red/green bicolor status indicator indicates the status of the adapter’s
connection to the end device.

MOD Status Indicator

This red/green bicolor status indicator indicates the status of the adapter.

Table 8 - Status Indicators and Descriptions

Status Indicator

Description

Page

PORT

End Device Connection Status

58

MOD

Adapter Status

58

NET A

EtherNet/IP network Connection Status

59

NET B

EtherNet/IP network Transmit Status

59

Status

Cause

Corrective Action

Off

The adapter is not powered or is not properly connected to
the end device.

Securely connect the adapter to the end device by using the 2100-ENET
adapter to DeviceNet cable.
Verify there are 24V DC across the two terminals on the green connector.

Flashing Red

The adapter is not receiving a ping message from the end
device.

Verify that cables are securely connected and not damaged. Replace cables
if necessary.
Cycle power to the end device and verify the end device powers up; for the
E3 Plus module, there is a green flash and then a red flash on powerup.

Steady Red

The end device has refused an I/O connection from the
adapter.

Important: Cycle power to the adapter after making any of the following
corrections:
Verify that the end device is supported by the adapter (that it is an E3 Plus
or 825-P at the appropriate firmware revisions. See

Getting Started on

page 9

).

Steady Orange

The adapter is connected to a product that is not supported.

Connect the adapter to a product that is supported by the adapter (for
example, an E3 Plus or 825-P at the appropriate firmware revisions).

Flashing Green

The adapter is establishing an I/O connection to the end
device.

No action required.

Steady Green

The adapter is properly connected and is communicating
with the end device.

No action required.

Status

Cause

Corrective Action

Off

The adapter is not powered or is not properly connected to
the end device.

Securely connect the adapter to the end device by using the 2100-ENET

adapter to DeviceNet cable.

Verify there are 24V DC across the two terminals on the green

connector.

Flashing Red

The adapter has failed the firmware test.
The adapter is being upgraded.

Cycle power to the end device.
If cycling the power does not correct the problem, update the firmware

to the latest firmware release.

Steady Red

The adapter has failed the hardware test.

Cycle power to the adapter.
Replace the adapter.

Flashing Green

The adapter is operational, but is not transferring I/O data to
a controller.

Place the scanner in RUN mode.
Program the controller to recognize and transmit I/O to the adapter.
Configure the end device for the program in the controller.

Steady Green

The adapter is operational and transferring I/O data to a
controller.

No action required.