Rockwell Automation 2100-ENET CENTERLINE 2100 Motor Control Centers EtherNet/IP Network Adapter User Manual

Page 29

Advertising
background image

Rockwell Automation Publication 2100-UM006A-EN-P - July 2013

29

Configure the I/O

Chapter 4

The bridge’s New Module dialog box appears.

8.

Edit the following.

9.

Click OK.

The bridge is now configured for the EtherNet/IP network and added to
the RSLogix 5000 project. It appears in the I/O Configuration folder. In
our example, a 1756-ENBT bridge appears under the I/O Configuration
folder with its assigned name. For convenience, keep the project open.
Later in this chapter, the project must be downloaded to the controller .

Box

Setting

Name

A name to identify the EtherNet/IP network bridge.

Description

Optional – description of the EtherNet/IP network bridge.

IP Address

The IP address of the EtherNet/IP network bridge.

Host Name

Not used.

Slot

The slot of the EtherNet/IP network bridge in the rack.

Revision

The minor revision of the firmware in the bridge. (You already set the major revision by
selecting the bridge series in

step 5

.)

Electronic
Keying

Compatible Keying. The Compatible Keying setting for Electronic Keying ensures the physical
module is consistent with the software configuration before the controller and bridge make a
connection. Therefore, verify that you have set the correct revision in this dialog box. Refer to
the online Help for additional information on this and other Electronic Keying settings. If keying
is not required, choose Disable Keying. Disable keying is recommended.

Open Module
Properties

When this box is checked, additional module properties dialog box appears to further configure
the bridge after clicking OK. When unchecked, the bridge’s New Module dialog box closes after
clicking OK. For this example, clear this box.

Advertising