Creating a new communications file – Rockwell Automation 2706-LSW DL40 PLUS OFFLINE PROG.SFTWR.USER MANUAL User Manual

Page 138

Advertising
background image

PLC-5 Data Pass–Through

D–6

Publication 2706-6.2

Select Create Communications File on the DH+ and Remote I/O
upload or download menus to create a new communications file

When creating or modifying a communications file, you must
provide the following:

DL40 Rack (Address) 0 to 76 (octal). The rack address assigned to
the DL40 using DIP Switch Bank #1.

DL40 Group (Number) First I/O Group Number assigned to the
DL40 using DIP Switch Bank #1 on the back of the DL40. Select: 0,
2, 4 or 6.

PLC Address 0 to 77 (octal). The station number of the PLC-5 on
the DH+ link to which the DL40 is attached. This address must
match the DIP switch settings on the PLC.

PLC Type Select: PLC-5/15, 25, 40, 60 or PLC-5/250. For
PLC-5/11, 5/20 and 5/30, choose PLC Type = PLC-5/15, etc.

Programming Terminal Address 0 to 77 (octal). Station number
for the programming terminal on the DH+ link.

DH+ Hardware Device You will have to provide additional data
depending on the type of interface module.

Creating a New
Communications File