Data format alarm example -4, Overrange -4 underrange -4, Open wire -4 cold junction compensation alarm -4 – Rockwell Automation 1797-IRT8 FLEX Ex Thermocouple/RTD/mV Input Module User Manual User Manual

Page 12: Data format alarm example, Overrange, Underrange, Open wire, Cold junction compensation alarm

Advertising
background image

Publication 1797-6.5.2 - February 2001

1-4 About the FLEX Ex Thermocouple/RTD/mV Input Module

Data Format Alarm Example

In this example, the normal active data range is 4-20mA. The alarms
are generated in three overlapping bands.

Overrange

If the input is greater than the maximum temperature of the
thermocouple or RTD range, millivolt (+100mV), or resistance (500W)
the overrange bit for that channel will be set.

Underrange

If the input is less than the minimum temperature of the thermocouple
or RTD range, millivolt (-40mV), or resistance (0W) the underrange bit
for that channel will be set.

Open Wire

Individual channel fault alarm for broken wire. If a broken wire/
detached lead is detected, the data value is forced to maximum. In
RTD/W mode, input levels above 540W will set this bit; in
thermocouple/mV mode, input levels above 210mV will set this bit.

Cold Junction Compensation Alarm

Broken or detached lead or shorted lead detection is included for
CJCs. This detection is only available when the input type selected is
thermocouple and sensor mode is set to CJC compensation.

When either CJC fails its fault is reported. Both CJCs ae normally used
in compensation calculations. If one CJC fails, calculations use the
remaining good device. If both fail, calculations use the last good
value.

normal signal range

overrange

CJC fault

underrange

Minumum

Value for

Sensor

Type

Maximum

Value for

Sensor

Type

Maximum

Measureable

Value

PHYSICAL INPUT SIGNAL RANGE

Channel Data

Forced to

Maximum for Type

CJC fault

open wire fault

Advertising