What this chapter contains, Status indicators, Chapter 7 – Rockwell Automation 1797-IRT8 FLEX Ex Thermocouple/RTD/mV Input Module User Manual User Manual

Page 65: What this chapter contains -1 status indicators -1, Chapter

Advertising
background image

1

Publication 1797-6.5.2 - February 2001

Chapter

7

Troubleshooting the FLEX Ex Thermocouple/
RTD/mV Input Module

What this Chapter Contains

Read this chapter to troubleshoot your I/O module.

Status Indicators

The 1797-IRT8 module has one status indicator for each input (8 in
all) and one power indicator that is on when power is applied to the
module .

For information on:

See page:

Status Indicators

7-1

Repair

7-2

Chapter Summary

7-2

Indicator

Color

State

Meaning

Status

Red

On

At power up – Channel 0 indicator lights at powerup until
all internal diagnostics are checked. After successful
powerup, the indicator goes off if no fault is present.
After successful powerup – Indicates a critical fault
(diagnostic failure, etc.)

Blinking (when
faults are
enabled, and bit
set)

Indicates a noncritical channel fault

Power

Off

Module not powered

Green

On

Module receiving power

Ex

1797-IRT8

PWR

A

B

C

A = Status indicators
B = Insertable labels for writing individual input designations
C = Power indicator

40070

Advertising