Chapter

3

How to Install Your FLEX Ex Thermocouple/
RTD/mV Module

What this Chapter Contains

Read this chapter to install the 1797-IRT8 thermocouple/RTD/mV
module.

Before You Install Your
Analog Module

Before installing your FLEX Ex analog module:

For information on:

See page:

Before You Install Your Analog
Module

3-1

Compliance to European Union
Directives

3-2

Installation in Zone 1

3-2

Removal and Insertion Under Power

3-3

Installing the Module

3-3

Connecting Wiring to the FLEX Ex
Thermocouple/RTD/mV Module

3-10

Grounding the Module

3-13

Chapter Summary

3-13

You need to:

As described under:

Verify that the module will be installed in a
suitable metal enclosure

Installation in Zone 1, page 3-2

Position the keyswitch on the
terminal base

Installing the Module, page 3-8

ATTENTION

!

These modules do not receive primary operational
power from the backplane. +/-V dc power must be
applied to your module before installation. If power
is not applied, the module position will appear to the
adapter as an empty slot in your chassis.