How to Install Your FLEX Ex Thermocouple/RTD/mV Module 3-3
Electrostatic Charge
Protect the system against electrostatic charge. Post a sign near this 
module: Attention! Avoid electrostatic charge. For your 
convenience, a sign which can be cut out and posted is included in 
this user manual before the back cover.
Removal and Insertion
Under Power
Installing the Module
Installation of this module consists of:
•
mounting the terminal base unit
•
installing the analog I/O module into the terminal base unit
•
installing the connecting wiring to the terminal base unit
If you are installing your module into a terminal base unit that is 
already installed, proceed to “Mounting the 1797-IRT8 Module on the 
Terminal Base” on page 8.
Mounting on a DIN Rail
ATTENTION
!
This module is designed so you can remove and 
insert it under power. However, take special care 
when removing or inserting this module in an 
active process. I/O attached to any module being 
removed or inserted can change states due to its 
input/output signal changing conditions.
ATTENTION
!
Make certain that you power this terminal base module 
combination with an instrinsically safe power supply. 
Do not exceed the values listed in the specifications for 
the terminal base or module.
Do not use the unused terminals on the terminal 
base unit. Using the terminals as supporting 
terminals can result in damage to modules and/or 
unintended operation of your system.
ATTENTION
!
Do not remove or replace a terminal base unit when 
power is applied. Interruption of the flexbus can 
result in unintended operation or machine motion.