Specifications

The following specifications apply to the 1797-IRT8 thermocouple/
RTD/mV input module.

Specifications - 1797-IRT8 Thermocouple/RTD Module

Number of Inputs

8 channels

IS Input Type

EEx ia IIB/IIC T4, AEx ia IIC T4, Class I, II, III Division 1 Group
A-G T4

IS Module Type

EEx ib IIB/IIC T4, AEx ib IIC T4, Class I, Division 1 & 2 Group
A-D T4

Input Type

Suitable for Pt 100, Pt200, Ni 100, Ni120, Ni200, 10Cu RTD,
thermocouple Type B, E, J, K, N, R, S, T, TXK/XK (L)
Configuration via internal bus

Signal Input Range

0 to 500 ohms; -40 to 100mV

Settling Time to 99% of Final
Value

8ms (mV mode,

o

F thermocouple)

Open RTD Detection

Out of range upscale reading

Lead Resistance
Compensation

< 15 ohm total

Transfer Characteristics

Accuracy

Temperature Effect

RTDs: 0.1% of span @ 20

o

C, filter cutoff < 1Hz

Thermocouples: 0.1% of span @ 20

o

C,

filter cutoff < 1Hz
Cold junction compensation = +1

o

C

150ppm/

o

C (primary range)

Indicators

8 red fault indicators
1 green module power indicator

Data Organization

Overrange Alarm
Lead Breakage Alarm
Fault State

Sensor Mode RTD 2,
3, or 4-wire,
TC Sensor Type (e.g. TC,
Type B, E, J..., RTD or
mV
Internal Reference
Junction (TC mode)

Individually for each channel
Individually for each channel
Individually for each channel (includes overrange, lead
breakage and short circuit)
Common to groups of 4 channels (ch 0-3, ch 4-7)

Common to groups of 4 channels (ch 0-3, ch 4-7)

Common to all channels (0

o

C, 20

o

C, 25

o

C, 30

o

C, 40

o

C, 50

o

C,

60

o

C, 70

o

C selectable

Output (intrinsically safe)
(16 position male/female
flexbus connector)

U

i

< 5.8V

I

i

< 400mA

Li = Negligible
Ci < 1.35

µ

F

Isolation Path
Input to power supply
Input to flexbus
Input to input
Power supply to flexbus

Isolation Type
Galvanic to DIN EN50020
Galvanic to DIN EN50020
None
Galvanic to DIN EN50020

Power Supply
(+V, -V intrinsically safe)

U

i

< 9.5V dc

I

i

< 1A

Li = Negligible
Ci = Negligible

Module Field-Side Power
Consumption

1.6W

Specifications continued on next page.