6-6 Applying FLEX Ex Thermocouple/RTD/mV Input Modules

Entity Parameters

Entity parameters are a system of quantified safe levels for voltage,
current, inductance, and capacitance used when connecting multiple
devices.

The following table details the entity parameters that must be taken
into account when designing a FLEX Ex system.

In the table above, power sources are devices such as outputs or
inputs, and power receivers are devices such as transmitters.

In use, the sum of all the input internal capacitance (C

i

) or internal

inductance (L

i

) in a control loop cannot exceed the allowed

capacitance (C

o

) or allowed inductance (L

o

).

Also, the open-circuit voltage (U

o

) or short circuit current (I

o

) cannot

exceed the maximum input voltage (U

i

) or maximum input current

(I

i

).

Table 6.B

Entity Terms:

Applied to:

CENELEC

FM/CSA

Maximum output (open-circuit) voltage

Power sources

U

o

V

oc

Maximum output (short circuit) current

Power sources

I

o

I

sc

Maximum allowed capacitance

Power sources

C

o

C

a

Maximum allowed inductance

Power sources

L

o

L

a

Maximum input voltage

Power receivers

U

i

V

max

Maximum input current

Power receivers

I

i

I

max

Maximum internal capacitance

Power receivers

C

i

C

I

Maximum internal inductance

Power receivers

L

i

L

I