Panel/wall mounting -6, Panel/wall mounting – Rockwell Automation 1797-IRT8 FLEX Ex Thermocouple/RTD/mV Input Module User Manual User Manual
Page 30

Publication 1797-6.5.2 - February 2001
3-6 How to Install Your FLEX Ex Thermocouple/RTD/mV Module
Panel/Wall Mounting
Installation on a wall or panel consists of:
•
laying out the drilling points on the wall or panel
•
drilling the pilot holes for the mounting screws
•
mounting the adapter mounting plate
•
installing the terminal base units and securing them to the wall
or panel
If you are installing your module into a terminal base unit that is
already installed, proceed to Mounting the 1797-IRT8 Module on the
Terminal Base Unit on page 3-8.
Use the mounting kit Cat. No. 1794-NM1 for panel/wall mounting.
To install the mounting plate on a wall or panel:
41547
Adapter Module
(not included)
Terminal Base Unit
(not included)
1
2
1.4
(35.5)
1 - Mounting Plate for Adapter
2 - 18 #6 self-tapping screws
(2 for the adapter, and 2
each for up to 8 modules)