About the FLEX Ex Thermocouple/RTD/mV
Input Module

What this Chapter
Contains

Read this chapter to familiarize yourself with the 1797-IRT8 input
module.

What the FLEX Ex
Thermocouple/RTD/mV
Modules Do

The 1797-IRT8 module accepts up to 8 thermocouple, RTD or mV
inputs. The inputs are nonisolated and are selected with analog
multiplexers which have a common-mode input range of -0.5 to +3.6
volts. The inputs will accept a millivolt or resistive input. Default input
spans are –40.00mV to +100.00mV or 0.00 to 500.00 ohms. Fault
Indicators are located on the field side.

No switches or jumpers are used on the thermocouple/RTD/mV input
module. The Inputs have both fixed hardware filters and selectable
firmware digital filters.

This module offers:

local microprocessor intelligence for advanced features

full functionality without switches or jumpers

multiple data ranges that can be independently programmed in
channel groups

lead breakage detection

overrange/underrange alarms

as well as a host of other module features.