About the FLEX Ex Thermocouple/RTD/mV 
Input Module
What this Chapter 
Contains
Read this chapter to familiarize yourself with the 1797-IRT8 input 
module.
What the FLEX Ex 
Thermocouple/RTD/mV 
Modules Do
The 1797-IRT8 module accepts up to 8 thermocouple, RTD or mV 
inputs. The inputs are nonisolated and are selected with analog 
multiplexers which have a common-mode input range of -0.5 to +3.6 
volts. The inputs will accept a millivolt or resistive input. Default input 
spans are –40.00mV to +100.00mV or 0.00 to 500.00 ohms. Fault 
Indicators are located on the field side.
No switches or jumpers are used on the thermocouple/RTD/mV input 
module. The Inputs have both fixed hardware filters and selectable 
firmware digital filters. 
This module offers:
•
local microprocessor intelligence for advanced features
•
full functionality without switches or jumpers
•
multiple data ranges that can be independently programmed in 
channel groups
•
lead breakage detection
•
overrange/underrange alarms
as well as a host of other module features.