Chapter summary, Data formats and fault modes -5, Chapter summary -5 – Rockwell Automation 1797-IRT8 FLEX Ex Thermocouple/RTD/mV Input Module User Manual User Manual
Page 13: Data formats and fault modes

Publication 1797-6.5.2 - February 2001
About the FLEX Ex Thermocouple/RTD/mV Input Module 1-5
Data Formats and Fault Modes
The tables below shows the bit settings for the data formats and fault
modes for your FLEX Ex thermocouple/RTD/mV module.
Data Formats
Fault Mode
Chapter Summary
In this chapter, we told you about the FLEX Ex system and the
thermocouple/RTD/mV module, and how it communicates with
programmable controllers.
Bit 11
10
09
08
Data type for channels 0 thru 7
0
0
0
0
o
C (see note)
0
0
0
1
o
F (see note)
0
0
1
0
o
K (see note)
0
0
1
1
-32767 to +32767
0
1
0
0
0 to 65535
0101 thru 1111 not used
Note: Module defaults to -4000 to 10,000 in millivolt mode, and 0 to 5000 in ohms mode
Bit
06
Fault enable for channels 0-3
07
Fault enable for channels 4-7
0 = disabled
1 = enable wire-off detection